Installation manual
Configuration
62
Remote Annunciator
Troubles related to the annunciator can have two possibilities: either the main panel and annunciator failed to
communicate with each other, or an unconfigured remote annunciator is responding to the main panel. In both the
cases, the following trouble message is displayed:
Four-wire smoke detector supply
The four-wire smoke detector supply is supervised for shorts. When a short is detected on the four-wire smoke
supply the power is cut off and a trouble message is generated. Press the system “RESET” key to restore power to
the system. If the short is removed, the panel will return to normal; otherwise the trouble message will stay.
RAU num mismatch
trouble 1/ 1
Trb:0x03 Info:0x0001
11:45 SAT 2003-02-03
Trouble Type
EVENT
01 of 09
DATE
TIME
"INFO " Key
Trouble code
Trouble info
"INFO " Key
4Wire Pwr. Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info