Installation manual
Configuration
56
Command Menu-->Dialer-Config
Time Parameters
Command Menu/Dialer-Config/Report Options
6.Dialer operation mode
[X] (U)DACT ->Default
[ ] DACT
Use this function to select the
functionality of the dialer. In
DACT mode only common
trouble/alarm/supervisory are
reported while in UDACT
mode all point information is
reported
Command Menu/Dialer-Config/Report Options
7.Checksum Bits
[X] 8 Bit ->Default
[ ] 16 Bits
Do not change this function;
keep it as default
For factory use only.
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Command Menu/Dialer-Config/Time Parameter
1.AC Loss delay
0 ->Default
0 to 20 hours
Use this function to delay the
reporting of AC loss trouble on the
dialer for the programmed time
period.
Command Menu/Dialer-Config/Time Parameter
2.Cellular report date
0 ->Default
Use this function to set the test report
date for the cell phone setup. If the
date is set to 0, there will be no test
reporting for cell phone or regular
telephone line. Other settings could
be anywhere from 01-28, representing
which day of the month the test
should be performed. When a cell
phone service is employed for the
panel, it should only be connected to
telephone line #2 CO interface. Also,
the dial tone detection feature of Line
#2 should be disabled for cell phone
application.
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
00:30 ->Default
Use this function to set the time for
auto test. This test has to be
performed once a day to send the test
report to the monitoring station. The
time is in 24hr format, which means
00:30 is 30 minutes after midnight.
Please avoid the following Test
Times: 00:00, 01.55, 02:00 and
03:00
Dialer Oper. Mode:
[X] (U)DACT
Checksum Bits:
[X] 8 Bits
1 AC-Loss Delay
2 Cellphone Date
3 Auto-Test Time
-Time Parameter-
AC-Loss Delay(Hrs)
0
Cellular Report Date
0
Auto-Test Time
00:30