Installation manual
FA-300 Series LCD Version Installation and Operation Manual
55
Command Menu-->Dialer-Config
Report Options
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Command Menu/Dialer-Config/Report Options
1.Alarm priority
[X] Account 1->Def
[ ] Account 2
Use this function to set the
account priority for reporting
alarms. If the priority is set for
account#1 then the dialer will
try account#1 first for
reporting.
Command Menu/Dialer-Config/Report Options
2.Trouble priority
[X] Account 1->Def
[ ] Account 2
Use this function to set the
account priority for reporting
trouble. If the priority is set for
account#1 then the dialer will
try account#1 first for
reporting.
Command Menu/Dialer-Config/Report Options
3.Supervisory priority
[X] Account 1->Def
[ ] Account 2
Use this function to set the
account priority for reporting
supervisory troubles. If the
priority is set for account#1
then the dialer will try
account#1 first for reporting.
Command Menu/Dialer-Config/Report Options
4.Aux Disconnect, Cancels Alarm &
Supv Reporting Thru dialer
[ ] ENABLE
[X] DISABLE ->Default
If this function is enabled, the
AUX DISCONNECT feature
(Command Menu, Item 12 as a
switch) will block the alarm
and supervisory events from
the being reported through the
built-in dialer.
Command Menu/Dialer-Config/Report Options
5.Fire Panel type
[X] FA-300 Panel->Def
[ ] FA-1000 Panel
[ ] FX-2000 Panel
Do not change this function;
keep it as default.
For factory use only.
1 Alarm Prio.
2 Trouble Prio.
3 Supv. Priority
4 Aux Dis Report
- Report Options -
5 Fire Panel
6 Operation Mode
7 Checksum Bits
Alarm Priority:
[X] Account 1
Trouble Priority:
[X] Account 1
SUPV Priority
[X] Account 1
AuxDis Alm&Supv Rpt.
[X] DISABLE
Fire Panel Type:
[X] FA-300 Panel