Installation manual

Configuration
42
Command Menu-->FA-300 Config
Inp Zone
This menu is used to program the process type for the initiating circuits. The maximum number of initiating circuits
supported is 12, but only those supported by the particular model will be shown.
Command Menu-->FA-300 Config
i
3
Zone
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Command Menu/FA-300 Config/Ipt. Zone
1. Type (Initiating circuit)
12.
[X] ALARM ->Default
[ ] VERIF ALARM
[ ] SPRKL ALM
[ ] WTR-FLOW ALM
[ ] NON-LATCH SUP
[ ] LATCH SUPV
[ ] GEN ALARM
[ ] MONITOR
[ ] TRB ONLY
Use this function to program
the process type of each input
zone. (See CIRCUIT TYPE
section for details.)
[ ] Zone-1->Default
.
.
.
[ ] Zone-12->Default
Use this function if i
3
devices
are present on a zone. (See i
3
devices section for details).
1 Zone-1
2 Zone-2
--
--
Initiating Zone
12 Zone12
Zone-1 Type
[X] ALARM
Zone-12 Type
[X] ALARM
[ ] Zone-1
[ ] Zone-2
--
--
I3 Detection Zones
[ ] Zone-12