Installation manual
Configuration
40
Command Menu/FA-300 Config/Features/
6.Signal-Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Use this function to inhibit the
“SIGNAL SILENCE” switch for a
desired length of time. This time
period should expire before the
signals may be silenced.
Command Menu/FA-300 Config/Features/
7. Aux. disconnect, disconnects
common alarm relay and common
supervisory relay
[ ] ENABLE
[X] DISABLE->Default
If enabled, this function will
disconnect (when selected by
Command Menu, Item 12 which
acts like an Aux. disconnect
switch) the Common Alarm
relay, the Common Supervisory
relay and the PR-300 will not
transmit a supervisory or alarm
event.
If disabled, selecting Aux
disconnect via the Command
Menu, Item 12 (which acts like
an Aux. disconnect switch) will
have no effect on the Common
Alarm relay, the Common
Supervisory relay and the PR-
300.
Command Menu/FA-300 Config/Features/
8.Auto Signal Silence Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
Use this function to determine
the time period for which the
indicating circuits will sound
before they are automatically
silenced.
Command Menu/FA-300 Config/Features/
9. Number of Remote
Annunciators or smart relays
[X] NONE->Default
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays
can be used as long as the
number does not exceed 6. The
annunciators’ addresses should
be linear: without gaps and in
sequence.
Command Menu/FA-300 Config/Features/
10.Silence Alarm transmit
[X] DISABLE ->Def
[ ] ENABLE
Use this function to allow the
alarm transmit and auxiliary
alarm relay to reset on “SIGNAL
SILENCE” rather than the
“RESET” switch.
Command Menu/FA-300 Config/Features/
11.AC power fail delay timer
[X] NONE ->Default
[ ] 8 HRS
[ ] 18 HRS
Use this function to delay the
AC power fail trouble for the
programmed time period. If
disabled, the AC power fail is
reported right away.
Command Menu/FA-300 Config/Features/
12.Common Supervisory Relay
[X] ENABLE ->Default
[ ] DISABLE
If disabled, the common
supervisory relay can be used
as common alarm relay. It will
act the same way as a common
alarm relay. If enabled, it is used
a common supervisory relay.
Sig-Sil. Inhibit Tmr
[X] DISABLE
Aux Dis,Dis Alm&Spv
[X] DISABLE
Auto Sig-Sil. Timer
[X] DISABLE
No. of Remote Annun.
[X] NONE
Alm. Xmit-Sil.
[X] DISABLE
AC Pwr Fail Dly Tmr.
[X] NONE
Common Supv. Relay
[X] ENABLE