Installation manual

FA-300 Series LCD Version Installation and Operation Manual
25
Figure 22: Power supply connection
Wiring Tables and Information
Table 3: Initiating Circuit Wiring
Wire gauge Maximum wiring run to last device
AWG Feet Meters
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
Notes:
For Class A the maximum wiring run to the last device is divided by two.
Maximum loop resistance should not exceed 100 ohms.
Maximum capacitance of 0.5uF total on each initiating circuit.
JW1
-+-+
SIG 3SIG 4
TO PR- 300 MO DULE
TO RM-312/RM -306 RELAY
MOD U LE
P1 P2
P3 P4
+
_
BATTERY
SEC. TX
blk
red
red
red
red
blk
+
+
_
_
Battery Battery
NOTE: TO PREVENT SPARKING, CONNECT BATTERIES AFTER THE
SYSTEM MAIN A.C. POWER IS TURNED ON
red
green
blk
yellow
240 VAC 50Hz
120 VAC 60Hz
N
GND