Installation manual
FA-300 Series LCD Version Installation and Operation Manual
17
Programming the relays
A typical relay circuit is shown below in Figure 8 with the jumper locations and descriptions.
Figure 10: RM-312/306 Relay programming
RM-306 Six Relay Adder Module
Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each
relay on the RM-306 are used to configure the relays. The jumpers located below the relays are used to select
either normally open contacts or normally closed contacts.
Figure 11: RM-306 six relay adder module
P1: Cable from RM-306 Relay Adder Module connects to P6 on the Main Fire Alarm Board.
Programming the relays
See explanation in Figure 8.
Note: Relay programming should be done before installing the board
Note: Relay programming should be done before installing the board
NO NC
SA
Z1
1&2
NO/ NC C
RELAY 1
NC/NO CONNECTION
NC: terminal provides normally closed contacts
NO: terminal provides normally open contacts
Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection
then the relay is not connected to the terminals
SUPV/ALARM SELECTION
S: Relay turns ON when common
supervisory is active
A: Relay turns ON when common
alarm is active
Default: No jumper installed,
connected on center pin only
ZONE JUMPER
installed: turns ON relay when the zone
(1) is active
removed: does not turn ON the relay when
zone (1) is active
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE
jumper installed: this relay 1 works in
conjunction with relay 2
jumper removed: relay 1 does not
operate with the adjacent relay 2
chaining example: if jumper is installed
on 1&2 and 2&3 then all the three relays
will be ON if any one of relays 1,2 and 3 is
active
Default: No jumper ins t a ll ed, connect ed
on one pin only
NO/NC C
RELAY 12
RELAY
LED (GREEN)
NO/NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/ NC C
RELAY 4
C
RELAY 5
NO/NC C
RELAY 6
NO/ NC
mounting hole
for #6-32 screws
mounting hole
for #6-32 screws
INDIVIDUAL GREEN
RELAY STATUS LEDs
Connect to P6 on the
main fire alarm board