Installation manual

DIP Switch and Jumper Selections for Main Board and Adder Modules
16
OCAC-304/302 Output Class-A Converter Adder Module
Figure 8: OCAC-304/302 Output Class-A Converter Adder Module
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For example indicating
circuit 1 positive (red wire) and negative (black wire) is wired from the Class A converter module to the positive and
negative terminals of Indicating circuit 1 on the Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then
wired back to the SIGNAL RET positive and negative.
Relay Adder Modules (Models RM-312 and RM-306)
RM-312 Twelve-Relay Adder Module
The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board. The jumpers located
above each relay on the RM-312 are used to configure the relays. The jumpers located below the relays are used to
select either normally open contacts or normally closed contacts.
Figure 9: RM-312 twelve relay adder module
P1: Cable from RM-312 Relay Adder Module connects to P6 on the Main Fire Alarm Board.
- SIG1 OUT +- SIG2 OUT+
- SIG1 R ET+- SIG2 RET+
BLK RED
BLK RED
mounting hole for
#6-32 screws
OCAC-302
mounting hole for
#6-32 screws
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 R ET+
BLK R ED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG4 R ET+
BLK R ED
BLK RED
mounting hole for
#6-32 screws
OCAC-304
mounting hole for
#6-32 screws
NO/NC C
RELAY 1
NO/NC C
REL AY 2
NO/NC C
REL AY 3
NO/NC C
REL AY 4
C
REL AY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
REL AY 8
C
REL AY 9
NO/NC C
REL AY 10
NO/NC C
REL AY 11
NO/NC C
RELAY 12
NO/NC NO/NC
Three mounting
holes for #6-32
screws
INDIVIDUAL
GREEN RELAY
STATUS LEDs
Connect to P6 on the
main fire alarm board