Specifications
FA-300-6L Installation and Operation Manual
59
Supervised Aux-supply
The supervised aux-supply is supervised for shorts. When a short is detected on supervised aux-supply the power
is cut off and a trouble message is generated. Press the system “RESET” key to restore the power the system. If
the short is removed, the panel will return to normal; otherwise the trouble message will stay.
City tie Polarity reversal - PR-300/ Relay module
The city tie or polarity reversal module is supervised for open and whether or not the PR-300 is plugged in. The
relay module is supervised for whether or not it is plugged in.
If any of the modules are not plugged in, the following trouble message is generated:
If there is an open detected on the city tie output, the following trouble message is displayed:
"INFO" Key
Aux. Power Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
"INFO" Key
CtyTie/RM312 missing
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
CityTie/RM306 missing
Active 1/1
"INFO" Key
City Tie trouble
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info