Specifications
Configuration and CFG-300 LCD Service Tool
52
Command Menu-->Dialer-Config
Report Options
Note: Refer to How to Use the Keypad to Program the FA-300 on page 34 for detailed instructions on
making menu selections.
Command Menu/Dialer-Config/Report
Options
1.Alarm priority
[X] Account 1->Default
[ ] Account 2
Use this function to set the
account priority for reporting
alarms. If the priority is set for
account#1 then the dialer will
try account#1 first for reporting.
Command Menu/Dialer-Config/Report
Options
2.Trouble priority
[X] Account 1->Default
[ ] Account 2
Use this function to set the
account priority for reporting
trouble. If the priority is set for
account#1 then the dialer will
try account#1 first for reporting.
Command Menu/Dialer-Config/Report
Options
3.Supervisory priority
[X] Account 1->Default
[ ] Account 2
Use this function to set the
account priority for reporting
supervisory troubles. If the
priority is set for account#1
then the dialer will try
account#1 first for reporting.
Command Menu/Dialer-Config/Report
Options
4.Aux Disconnect, Cancels Alarm
& Supv Reporting Through dialer
[ ] ENABLE
[X] DISABLE ->Default
If this function is enabled, the
Aux Disconnect feature
(obtained by pressing the Aux
Disconnect button) will block
the alarm and supervisory
events from being reported
through the built-in dialer.
-Report Options-
1. Alarm Prio.
2. Trouble Prio.
3. Supv. Prio.
4. Aux. Dis Report
5. Operation Mode
Alarm Priority:
[X] Account 1
Trouble Priority:
[X] Account 1
SUPV Priority
[X] Account 1
AuxDis Alm/Supv Rpt.
[X] DISABLE