Specifications
System Checkout
30
System Checkout
Before Turning the Power On
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the main AC
supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC supply.
Power-Up Procedure
1. After completing the above procedures, power-up the panel. The green AC ON LED and the Common Trouble LED should
illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the Battery/Charger Trouble LED should illuminate,
the trouble buzzer should sound intermittently, and the Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity: the red wire is positive (+) and the black wire is negative (-). All
indicators should extinguish except for the AC ON LED.
4. Configure the fire alarm control panel as described in System Configuration on page 40.