Specifications
Field Wiring
24
Signal Module (SGM-1004A) Terminal Connections
Wire devices to terminals as shown in Figure 20 below. For more information see Wiring Tables and Information on
page 29, Appendix B: Device Compatibility List on page 50 for compatible devices, and Appendix C: Module
Specifications and Features on page 57.
Figure 20 Signal Module (SGM-1004A) Terminal Connections
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• SGM-1004A indicating circuits are fully supervised and rated for 24 VDC unfiltered, 1.70 amp max. They
must be wired as shown in Table 5
• The terminal blocks are "depluggable" for ease of wiring.