Operator`s manual

FA-265 Installation and Operator’s Manual
29
1. Enter the programming mode by pressing and holding the Walk Test switch for 2 seconds.
2. Press any switch. To silence the trouble buzzer and enter the Section 0 programming.
3. Press and hold the Lamp Test switch for 2 seconds.
4. The Common Supervisory LED flashes to indicate the View Buffer mode.
5. Events are shown from the most recent to the oldest.
6. See the event table below which indicates the LED patterns used to indicate various events.
7. To advance to the next event press the Silence Trouble switch.
8. Once all 20 events have been viewed, the next Silence Trouble keypress will exit the view buffer mode
and return to the Section 0 programming. To exit the programming mode, press and hold for 2 seconds the
Walk Test switch.
9. Pressing the Silence Signal switch at any time will cause the system to exit the View Buffer mode. The
buzzer will sound. Press any button to go to the Section 0 programming mode.
50/60 Hz Option- Section 5 (Signal Silence LED on steady)
Reset Section Programming (All common trouble LEDs flashing)
To Enter this Programming Section
1. Enter the installer programming mode, section 0
2. Press and hold the System Reset button for 2 seconds. The Z1 ALM LED and TRB LED will be ON
and all the System Trouble LEDs will flash.
To Remove Module
Physically remove the module from the system and enter the reset section programming as described
above. Press the ‘Silence Alarm’ button until the Z1 SUPV LED is ON. Press the ‘Silence Trouble
button to exit this section. Upon exit, the system will reset the ‘supervision’ field for all the modules
currently connected to the ‘secur-bus’.
To Add a Module
Just connect it to the system and it will auto-enroll within one minute.
To Default the System
Enter the reset section programming as described above. Press the
‘Silence Trouble’ button until the Z2 ALM LED is ON and Z2 TRB LED is
ON. Press the ‘Silence Alarm’ button until the Z2 SUPV LED is ON.
Press the ‘Silence Trouble’ to exit this section. Upon exit, the system will
reset all of the panel programmable parameters to their factory default
state. Please note that the ‘supervision’ field will be reset as well.
ALARM
Do not
default (Z2)
(Factory default
)
Default to factory
program (Z2)
SUPV TRB