5.5.1 Configure
The configure page is designed to set the configurable values of the UPS and/or SNMP card.
These values will be stored in the UPS and/or SNMP card.
Note: Different UPS models support different configuration options.
5.5.1.1 Auto Restart
The card sends the command to the UPS to configure the auto restart function.
5.5.1.2 UPS Buzzer
The card sends the command to the UPS to configure the buzzer function.
5.5.1.3 Low Battery
The set value is compared to the received value from the UPS. If the received battery
level is lower than the assigned value then the card sends the Low Battery Warning.
5.5.1.4 UPS Shutdown Action
The set value is compared to the received value from the UPS. If the Power Fail or Low
Battery event occurs then the card sends the assigned shutdown delay time to the UPS.
5.5.1.5 Smart Shutdown
Initiates a signal for the server to shutdown. After the user-defined Estimated OS
Shutdown Delay, the output power is switched off. SNMP-NV6 Client or SNMP
ShutdownAgent must be used on the server for it to be properly shutdown. The
Estimated OS Shutdown Delay includes the assigned countdown delay in the shutdown
software plus the duration of OS shutdown process. When the Shutdown Agent receives
the Smart Shutdown signal, the low battery settings will be used to process the shutdown
procedure.