User`s manual
33
SNMP Trap Number
Variable Trap No. Description
dupsCommunicationLost 1 SEVER: Communication with the UPS failed
dupsCommunicationEstablished 2 INFORMATION: Communication with the UPS reestablished
dupsPowerFail 3 WARNING: Power failed. The UPS is operating on battery power
dupsPowerRestored 4 INFORMATION: Power restored. The utility power restored
dupsLowBattery 5 SEVER: The UPS batteries are low and will soon be exhausted
dupsReturnFromLowBattery 6 INFORMATION: The UPS has returned from a low battery condition
dupsLoadWarning 7 INFORMATION: Loading percent of the UPS over the Load Warning value
dupsNoLongerLoadWarning 8 INFORMATION: Returned from Load Warning condition
dupsLoadSeverity 9 Warning: Loading percent of the UPS over the Load Severity value
dupsNoLongerLoadSeverity 10 INFORMATION: Returned from Load Severity condition
dupsLoadOnBypass 11 WARNING: The UPS loads on bypass
dupsNoLongerLoadOnBypass 12 INFORMATION: The UPS is not on bypass mode
dupsUPSFault 13 SEVER: A general fault caused in the UPS
dupsBatteryGroundFault 14 SEVER: The UPS battery ground fault
dupsNoLongerBatteryFault 15 INFORMATION: The UPS recovered from battery ground fault
dupsTestInProgress 16 INFORMATION: The UPS test in progress
dupsBatteryTestFail 17 SEVER: The UPS battery test failed
dupsFuseFailure 18 SEVER: The UPS fuse failed
dupsFuseRecovered 19 INFORMATION: The UPS fuse recovered
dupsOutputOverload 20 SEVER: The UPS overload
dupsNoLongerOverload 21 INFORMATION: Recovered from UPS overload
dupsOutputOverCurrent 22 SEVER: The UPS output over-current
dupsNoLongerOutputOverCurrent 23 INFORMATION: Recovered from UPS over-current
dupsInverterAbnormal 24 SEVER: The UPS inverter abnormal
dupsInverterRecovered 25 SEVER: Recovered from UPS inverter abnormal
dupsRectifierAbnormal 26 SEVER: The UPS rectifier abnormal
dupsRectifierRecovered 27 INFORMATION: The UPS recovered from rectifier abnormal
dupsReserveAbnormal 28 SEVER: The UPS reserve abnormal
dupsReserveRecovered 29 INFORMATION: The UPS reserve recovered
dupsLoadOnReserve 30 INFORMATION: The UPS load on reserve
dupsNoLongerLoadOnReserve 31 INFORMATION: The UPS no longer load on reserve
dupsEnvOverTemperature 32 WARNING: The environment over-temperature
DupsNoLongerEnvOverTemperature 33 INFORMATION: The environment recovered from over-temperature
DupsEnvOverHumidity 34 WARNING: The environment over-humidity
DupsNoLongerEnvOverHumidity 35 INFORMATION: The environment recovered from over-humidity