Owners manual
RPM1521E
20
3-2-4 Schedule
Schedule the outlet to turn ON/OFF or Reboot on a certain day at a specific time.
Period: An Action can be schedule to occur yearly, monthly, weekly or daily at a specific
time for each individual outlet.
Time: Set the time (hours and minutes) when you want the Action to occur.
Action: Set the action you want the outlet to perform, ON, OFF or Reboot.
Delete: To delete a schedule, double-click on the “X”.
Add: Click the ADD button to add this action.
Save: Once the setup is complete click the Save button to save all of the changes.
3-2-5 Auto-Ping
The RPM1521E can be setup to ping an IP-addressable device and detect when that
device has stopped communicating. If the Reboot action is selected the power to the
connected device will be cycled OFF and then ON. After the preset time the Auto-Ping
function will restart.
Ping: Check this box to enable the Auto-Ping function.
Host: Enter the IP address of the device to ping.
Ping Interval Time: Set the time Interval to PING the connected device.
Ping Times: If a device fails to respond to a ping continuously and exceeds the preset time,
the RPM1521E will notify the selected personnel via email or SMS.
Reboot: Check this box to reboot the outlet for the failed connected device.
Re-Ping Time: The time interval before restarting the Auto-Ping function after the
connected device has been rebooted.
Save: Once the setup is complete click the Save button to save all of the changes.