2. Installation and Setup
2-1 Hardware Installation
The RPM1521E is intended to be installed in a temperature controlled environment that is
free of conductive contaminants. Select a location, which will provide good air circulation
for the RPM1521E at all times. Avoid locations near heating devices, water or excessive
humidity, or where the RPM1521E is exposed to direct sunlight. Route power cords so
they cannot be walked on or damaged.
CONNECTING THE RPM1521E TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes
maximum branch circuit over-current protection in accordance with the National Electric
Code, ANSI/NFPA 70. Plug the RPM1521E into a two pole, three wire, grounded
receptacle only. Do not use extension cords, adapter plugs, or surge strips. Do not
plug the RPM1521E to the output of a Simulated Sine Wave UPS.
1. Connect the power cord to the power inlet on the RPM and to the utility service.
2. Plug the equipment into the output receptacles.
3. Connect the Ethernet cable to the Ethernet port.
4. Connect the Temperature probe (optional)
5. Turn the power switch to the ON position.