ELECTRICAL GENERAL PROVISIONS 260001 – 7
3.8 FIRE PENETRATION SEALS:
A. Seal all raceway and/or cable penetrations through fire-rated floors, wall, and ceilings to prevent
the spread of smoke, fire, toxic gas or water through the penetration either before, during or
after fire. Provide penetration sealants and fittings of ratings to match the rating of the
penetrated materials so that the original fire rating of the floor or wall is maintained as required
by Article 300-21 of the NEC.
B. Sealant Systems: Provide sealants, wall wraps, partitions, caps, and other accessories
complying with UL 1479 (ASTM E-814) from the following where applicable:
1. 3M Fire Barrier Sealing Penetration System
2. Chase Foam Fire Stop System
3. Thomas and Betts Flame Safe Fire Stop System
4. Nelson Fire Stop Products
C. Fittings: Where applicable, provide OZ Type CFSF/I and CAFSF/I fire seal fittings for conduit
and cable penetrations through concrete and masonry wall, floor, slabs, and similar structures.
D. Install sealants and fittings in accordance with all manufacturer's written instructions.
3.9 LABELING:
A. Engraved black plastic laminated, with white-core labels, 1/16" thick, shall be permanently
3.10 TESTS:
A. Notify engineer prior to all testing specified herein at least three business days prior to testing.
Engineer shall observe all tests to insure the proper operation of the electrical system.
3.11 PROJECT FINALIZATION AND START-UP:
A. Upon completion of the work, have each factory representative and/or subcontractor assist in
start-up and testing of their respective systems.
B. Have each representative give personal instructions on operating and maintenance of their
equipment to the owner's maintenance and/or operation personnel.
C. Have representatives certify each system with a written statement indicating that they have
performed start-up and final check out of their respective systems.
3.12 FINAL REVIEW:
A. Have the project foreman accompany their reviewing parties and remove coverplates, panel
covers, access panels, etc. as requested, to allow review of the entire electrical system.
END OF SECTION 260001