Specifications

Draper Prison Wasatch & Oquirrh Intercom & Paging System Remodel 4-21-2014
PUBLIC ADDRESS SYSTEMS 275116 - 5
a. Turn on the LED for the same button on the control panel;
b. Route panel 1 microphone to Level 1 Day Room speakers;
c. Un-mute level 1 Day Room speakers;
d. Send a one second long pre-announcement tone to level 1 Day Room speakers;
2. Release the Day Room button after making an announcement, the system shall:
a. Mute level 1 Day Room speakers;
b. Turn off LEDs for the level 1 Day Room buttons;
D. Level 2 Day Room paging, level 3 Day Room paging:
Refer to the programming for level 1 Day Room paging above.
E. Level 1 Monitoring:
1. Push down Monitor button to turn on the monitoring system to listen and the system shall:
a. Turn on Level 1 Monitor button LED;
b. Route Level 1 Dayroom microphone to Level 1 panel speaker;
c. Unmute Level 1 Dayroom microphone;
2. Push the Monitor button one more time to turn off the monitoring system and the system
shall:
a. Turn off Level 1 Monitor button LED;
b. Mute Level 1 Dayroom microphone;
F. Level 2 and Level 3 Monitoring:
Refer to the programming for Level 1 monitoring above.
G. Lamp Test Button on Level 1 panel:
1. Push Lamp Test button on level 1 panel and the system shall:
a. Turn on all LEDs on the panel;
2. Release the Lamp Test button and the system shall:
a. Turn off all LEDs on the same panel;
H. Key Switches:
1. Rotate panel 1 Key Switch to left or right and the system shall:
a. Turn on power supplies (including existing ones) to the panel.
2. Rotate panel 1 Key Switch to the other side and the system shall:
a. Turn off power supplies (including existing ones) to the panel.
I. Lamp Test button and Key Switch on other panels:
Refer to the programming for level 1 Lamp Test buttons and Key Switches above.
J. Modify the program as requested by the owners’ representatives or by the AV consultant.
2.3 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design supports and seismic restraints for control consoles, equipment
cabinets and racks, and components, including comprehensive engineering analysis by a
qualified professional engineer, using performance requirements and design criteria indicated.
B. Seismic Performance: Supports and seismic restraints for control consoles, equipment cabinets
and racks, and components shall withstand the effects of earthquake motions determined
according to ASCE/SEI 7.
Bid DA14027DFCM
5/30/2014 2:08 PM p. 103