Technical data
TROUBLESHOOTING
CV ELECTRICAL POWER SYSTEM MAINTENANCE MANUAL 2A5A2-ELEC-MM-1-0 37
5.5 HPU Power #1 or #2 Doesn't Work
Procedure
1. Follow the troubleshooting steps in Figure 4.
0.
Yes
Voltage OK?
No
At the HPU #1 or #2 boost transformer input, measure voltage
for each phase (3):
Negative Probe Positive Probe Acceptable Readings
øA tap 480
øA tap 480
øB tap 480
øB tap 480
480 ± 48 VAC
øC tap 480 480 ± 48 VAC
øC tap 480 480 ± 48 VAC
Replace HPU boost transformer
(see Section 4.5, Replacing an
HPU Boost Transformer)
Problem is upstream ( see PRMS-
MSE-AE Deck Interconnects-Electrical
Maintenance Manual (2A13A9-
INCONELEC-MM), Troubleshooting)
Figure 4 Troubleshooting – HPU Power #1 or #2 Doesn't Work