CV ELECTRICAL POWER SYSTEM MAINTENANCE MANUAL 2A5A2-ELEC-MM-1-0 35
5.3 PRM Hotel Power #1 Doesn't Work
Procedure
1. Follow the troubleshooting steps in Figure 2.
0.
No
Problem
solved?
Yes
Yes
Voltage OK? No
At PRM hotel power #1 UPS, measure voltage at the input:
Negative Probe Positive Probe Acceptable Reading
L1 L2 208 ± 21 VAC
Yes
Voltage OK? No
At PRM hotel power #1 UPS, measure voltage at the output:
Negative Probe Positive Probe Acceptable Reading
L1 L2 208 ± 21 VAC
Done
At the 208/120 VAC 3ø distribution panel
#1, reset breaker hotel power #1 UPS.
At the power room, reset hotel power UPS.
Replace PRM hotel power #1 UPS
(see Section 4.9, Replacing the
Hotel Power UPS)
Replace hotel #1 boost transformer
(see Section 4.6, Replacing a Hotel
Boost Transformer)
Follow decision tree in Section 5.2,
Troubleshooting Subroutine – 10 kVA
480-208/120 VAC 3ø Transformer #1 or
#2 Power Check
Figure 2 Troubleshooting – PRM Hotel Power #1 Doesn't Work