Technical data
TROUBLESHOOTING
CV ELECTRICAL POWER SYSTEM MAINTENANCE MANUAL 2A5A2-ELEC-MM-1-0 34
5.2 Troubleshooting Subroutine — 10 kVA 480-208/120 VAC 3Ø
Transformer #1 or #2 Power Check
Procedure
1. Follow the troubleshooting steps in Figure 1.
0.
At the 10 kVA 480-208/120 VAC 3ø transformer #1 or #2,
measure voltage at the input:
Yes
Voltage OK? No Done
Measure voltage at output:
Yes
Voltage OK? No
Negative Probe Positive Probe Acceptable Readings
øA
øA
øB
øB 480 ± 48 VAC
øC 480 ± 48 VAC
øC
480 ± 48 VAC
Negative Probe Positive Probe Acceptable Readings
N
N
N
øA 120 ± 12 VAC
øB 120 ± 12 VAC
øC 120 ± 12 VAC
Problem is upstream ( see PRMS-
MSE-AE Deck Interconnects-Electrical
Maintenance Manual (2A13A9-
INCONELEC-MM), Troubleshooting)
Replace transformer (see Section 4.7,
Replacing a Service Transformer)
Return to decision tree that
requested this subroutine
Figure 1 Troubleshooting Subroutine – 10 kVA 480-208/120 VAC 3Ø Transformer #1
or #2 Power Check