STYLE 7: "Daisy Chained" Configuration
(Must be performed by Authorized Service Personnel ONLY)
1. Be sure to read the installation placement procedure, the cautions section,
the safety precautions section and the Configuration Style for your Battery
Pack before Daisy Chaining the Battery Pack(s).
2. Make sure that all the Battery Pack's circuit breakers and UPS's power
switch, are in OFF position. Unplug all the equipment that is plugged into the
UPS's output receptacles. Disconnect the power cords that are on the
Battery Packs and the UPS from the AC outlet.
3. Remove the self-stick protective strip from the rear of the UPS and from the
rear of the Battery Packs. Use CAUTION when removing the self-stick
protective strip from the UPS's battery connector and the Battery Pack's
connector; the battery voltage is present at the connector's contacts. If the
UPS's battery connector or the Battery Pack's connector is not being used,
the self-stick protective strip should not be removed.
4. Before plugging the battery cable (provided) into the UPS's external battery
connector/terminal block or the Battery Pack's connector/terminal block, verify
that they mate red (positive) to red (positive) and black (negative) to black
(negative).
5. Connect one end of the Battery Cable to the Battery Pack's connector/
terminal block and secure by tightening the screws (do not over tighten).
6. Connect the other end of the battery cable to the UPS's battery connector/
terminal block and secure by tightening the screws (do not over tighten).
10.
CAUTION: If you reverse steps #5 and #6 or if the Battery Pack's circuit
breaker is in the ON position, the open end of the battery cable will have
battery voltage at the connector's contacts. To avoid this, follow the
procedure in the correct order.
7. Connect the next battery cable to the first Battery Pack's unused battery
connector/terminal block and secure by tightening the screws (do not
overtighten).
8. Connect the other end of the battery cable to the next Battery Pack's battery
connector/terminal block and secure by tightening the screws (do not
over tighten).
9. Connect the next battery cable to the last Battery Pack's unused battery
connector/terminal block and secure by tightening the screws (do not
overtighten).
Connect the other end of the battery cable to the next Battery Pack's
battery connector/terminal block and secure by tightening the screws (do
not over tighten).
"Daisy Chained" means hooking one Battery Pack to another Battery Pack
to another Battery Pack; this chain could go on indefinitely. Follow the steps
below to Daisy Chain the Battery Packs.