User`s manual

20
English
WARNING: Use two or more people when installing the Battery Pack(s)
and the UPS into the rack (see the UPS User's Manual for rack
mounting the UPS). Use caution; these units are extremely heavy. Do
not move the rack after the units have been installed. The rack may be
unstable due to the weight distribution.
1. Make sure that the circuit breakers on both the UPS and the Battery Pack(s)
are in OFF position.
2. Make sure that the UPS's power switch is in the OFF position.
3. Make sure that the input circuit breaker (at the wall breaker box) is in the
OFF position.
4. Remove the External battery connector's access panel from the back panel
of the UPS and from the back panel of the Battery Pack(s). Use CAUTION
when removing the External battery connector's access panel from the
UPS's and the Battery Pack's back panel; the battery voltage is present
at the External battery connector's contacts. If the UPS's battery connector
or the Battery Pack's connector is not being used, the External battery
connector's access panel should not be removed.
5. Before plugging the battery cable (provided) into the UPS's external battery
connector or the Battery Pack's connector, verify that they mate red to red
and black to black.
6. Connect one end of the Battery Cable to the Battery Pack's connector and
secure by tightening the strain relief screw (do not over tighten).
7. Connect the other end of the battery cable to the UPS's battery connector
and secure by tightening the strain relief screw (do not over tighten).
CAUTION: If you reverse steps #6 and #7 or if the Battery Pack's circuit
breaker is in the ON position, the open end of the battery cable will have
battery voltage at the connector's contacts. To avoid this, follow the
procedure in the correct order.
8. Verify that all the connections are secure and that the polarity is correct.
9. The UPS system is now ready for the normal start-up procedure (see the
UPS User's Manual). On all the units that were installed, check that all the
switches and all the circuit breakers are in the ON position.
Note: For the installation of multiple Battery Packs see STYLE 7: "Daisy
Chained" Configuration.