User`s manual
14
English
6. Make sure that both the Battery Pack's circuit breaker and UPS's power
switch are in off position. Unplug all the equipment that is plugged into the
UPS's output receptacles. Disconnect the power cords that are on the
Battery Pack(s) and the UPS from the AC outlet.
7. Remove the self-stick protective strip from the rear of the UPS and from the
rear of the Battery Pack(s). Use CAUTION when removing the
self-stick protective strip from the UPS's battery connector and the
Battery Pack's connector; the battery voltage is present at the connector's
contacts. If the UPS's battery connector or the Battery Pack's
connector is not being used, the self-stick protective strip should not be
removed.
8. Before plugging the battery cable (provided) into the UPS's external
battery connector or the Battery Pack's connector, verify that they mate red
to red and black to black.
9. Connect one end of the Battery Cable to the Battery Pack's connector and
secure by tightening the thumb bolt screws (do not over tighten).
Connect the other end of the battery cable to the UPS's battery connector and
secure by tightening the thumb bolt screws (do not over tighten).
Once the location and position of the Battery Pack(s)
and the UPS have been determined, lay the Battery
Pack(s) down flat. Align the mounting bracket with
the mounting bracket screw holes and attach with
the retaining screws. Use the template to mark the
bolt hole position on the wall. CAUTION: You should
always were protective gear for your hands and eyes
when operating power tools.
Drill the holes for the
bolts and make sure that all of the holes are drilled
into structural material. Then clean the area of any
loose material. Install the four bolts into the bolt holes.
Do not tighten the bolts all the way, leave
approximately 3/8" of the bolt sticking out. Position
the Battery Pack so that the mounting bracket keyed
holes line up with the four bolts. Slide the Battery
Pack down until its resting securely on the four bolts. Tighten the four bolts
to secure the Battery Pack to the wall. Go to step #6 on page 14 and finish
the rest of this procedure to install the Battery Pack(s).
WARNING: Use two or more people when installing the Wall Mount
Battery Pack(s) and the UPS (see the UPS User's Manual for Wall
Mounting the UPS). Use caution; these units are heavy.
10.
CAUTION: If you reverse steps #9 and #10 or if the Battery Pack's circuit
breaker is in the ON position, the open end of the battery cable will have
battery voltage at the connector's contacts. To avoid this, follow the procedure
in the correct order.