Specifications
Unistar Sx Series UPS
Form No. 003-2077
18
CAUTION:CAUTION:
CAUTION:CAUTION:
CAUTION: System voltages range from 24 VDC to 288 VDC. A battery can present a risk of
electrical shock and high short circuit current. The following precautions should be
observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery terminals.
6. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source
of the ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance.
CAUTION: CAUTION:
CAUTION: CAUTION:
CAUTION: Replace batteries with the same number and type as originally installed in the UPS.
These batteries have pressure operated vents. When replacing the batteries, replace
with the same number of the:
Manufacturer Model Number
CSB GP/FR 12070 F2
YUSA NP7-12\250
PANASONIC LCR 12V 7.2S1
HITACHI HV7-12 F2
These batteries are used in both the UPS and external Battery Packs.