Code Definition
E01 System off resulting from Microprocessor check sum error.
E03 Battery voltage is below safe operating range (AC mode).
E04 Battery voltage has exceeded safe operating range (AC mode).
E05 Thermal sensor is dead or unit exceeds safe temperature.
E10 Configuration dip switch is in the off position.
E13 Input/Output voltage difference is out of 6V specification (AC tracking mode).
E22 +DC bus voltage is out of the range of +15% to -10%.
E23 -DC bus voltage is out of the range of +15% to -10%.
E24 Phase unlocks between input and output.
E32 Power is over 100% for 60 seconds.
E32 Power is over 125% for 10 seconds.
E32 Power is over 150%.
E32 Power is over 300%
E32 RMS current is over 100% for 60 seconds.
E32 RMS current is over 125% for 10 seconds.
E32 RMS current is over 150% for 3 seconds
E32 RMS current is over 300%
E32 Power is over 100% or RMS current is over 100% for 5 seconds (DC mode).
E32 Power is over 125% (DC mode).
E40 Temperature is out of range.
E52 Output senses a short circuit.
E53 Battery test error (battery may be bad or needs charge time).
E55 Input voltage is over 150Vrms for 120vac units.
Diagnostic codes not listed are used by Engineering staff for programming purposes.
If your unit should have a problem, please call our Customer Service department to resolve any
issues. Please call, 866-261-1191 or 937-253-1191 and ask for Technical Support. When you
call with a problem, please be prepared to provide the following information to the technician.
Model number: example: SB30001
Model Serial number: example: E3026 (5 characters)
Length in Service: example 25 months
Diagnostic code at time of problem: example: E32
Time of day during failure: example: 4:15 am
Weather conditions during failure: example: clear skies, no power problems.