Unistar Sx Series UPS Form No. 003-2077 TABLE OF CONTENTS 1 INTRODUCTION ............................................................................................. 1 2 CONTROLS AND INDICATORS ..................................................................... 3 3 INSTALLATION ............................................................................................... 5 4 OPERATION ...................................................................................................
Unistar Sx Series UPS Form No. 003-2077 1 INTRODUCTION Thank you for purchasing a Staco Energy Products power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORT ANT SAFETY INSTRUCTIONS IMPORTANT SA VE THESE INSTRUCTIONS! SAVE Please read the manual before installing your UPS.
Unistar Sx Series UPS Form No. 003-2077 The packing materials that your UPS was shipped in, are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to Staco Energy Products, please use the original packing material. Since Staco Energy Products is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive VE THE P ACKING MA TERIALS! insurance.
Unistar Sx Series UPS Form No. 003-2077 2 CONTROLS AND INDICA TORS INDICAT FRONT P ANEL (LCD Units) PANEL Primary Power Switch: Press and release the ON/OFF button to turn the unit ON or OFF. Normal Mode Icon: This icon will illuminate when the utility power is within safe operating range. Battery Mode Icon: This icon will illuminate when the Utility power is outside safe operating range and the unit is operating in the battery mode.
Unistar Sx Series UPS Form No. 003-2077 Unit Input Icon: When selected, this will display the selected item for the input from utility. Unit Output Icon: When selected, this will display the selected item for the output from unit. Unit Amperage Icon: When selected, this will display the amps from either the input or output based on selection of input or output as described previously.
Unistar Sx Series UPS Form No. 003-2077 3 INST ALLA TION INSTALLA ALLATION INST ALLA TION PLACEMENT INSTALLA ALLATION English Install the UPS in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.
Unistar Sx Series UPS Form No. 003-2077 Fans Maintenance Bypass Switch Smart Slot Output Circuit Breakers Alarm Silencer RS232 Port Contact Closure Port Configuration Switches Access Panel for Input/Output Terminals SB50002 and SB70002 Fans: Internal Cooling Fans. Maintenance Bypass Switch: In normal operation the switch must be in the UPS position. When doing routine maintenance the switch must be in the BPS position. Output Circuit Breakers: Turn OFF/ON the output of the UPS.
Unistar Sx Series UPS Form No. 003-2077 INST ALLA TION INSTALLA ALLATION (Must be performed by Authorized Service Personnel ONLY) Be sure to read the installation placement and all the cautions before installing the UPS. The MCP-E series UPS has external Battery Pack capability, please observe the following warning when connecting the Battery Pack(s). WARNING! DO NOT PLUG THE BATTERY PACK'S CONNECTOR INTO THE UPS's BATTERY CONNECTOR WHILE THE UPS IS TURNED ON.
Unistar Sx Series UPS Form No. 003-2077 NOTE: The SB50002 and SB70002's AC input must be connected to an AC circuit breaker which will provide for an emergency power off. (Must be performed by Authorized Service Personnel ONLY). Model S B 50002 S B 70002 Input Circuit Breaker 40 Amp 50 Amp Input Wire Size/Temp 8 AWG/105°C 6 AWG/105°C Wire Conductor Three conductor, copper wire only Tightening torque for pressure wire connectors having screws Torque 17.
Unistar Sx Series UPS Form No. 003-2077 The Unistart Sx Series UPS can be installed in two different configurations. The Tower Model allows the user to install the UPS next to the tower computer. Use CAUTION, the UPS is extremely heavy. Place the UPS in the final desired location and complete the rest of the installation procedure. Now the UPS is ready for the normal start-up procedure. The Rackmount Configuration comes with mounting brackets for the standard 19" (46.5cm) rack.
Unistar Sx Series UPS Form No. 003-2077 NETWORK SURGE PROTECTION CONNECTION (OPTIONAL) Connect a 10 Base-T network line to the protection sockets on the rear of the UPS (not available on all models). This connection will require another length of network cable. The cable coming from the networked system is connected to the port marked “IN”. The “OUT port is connected to the equipment to be protected. NOTE: Connecting to the Network Surge Protection connection is optional.
Unistar Sx Series UPS Form No. 003-2077 SB20001/2 and SB30001/2. RS232 Port, Control Port pinouts and Configuration Switches. Configuration Switches for the SB 2000/3000/5000/7000. The "System Enable" switch must be enabled for the UPS to operate.
Unistar Sx Series UPS Form No. 003-2077 Place your unit in the desired location for use. Connect all equipment power cords to the receptacles on the rear of the UPS. Please insure you confirm total power requirements and do not overload the units. Press and release the main power switch on the front of the unit to turn on the unit. Press and release again to turn off the unit.
Unistar Sx Series UPS Form No. 003-2077 Communications port information for 2KVA, 3KVA, 5KVA and 7KVA units only: These units contain two independent communications ports. Port one is for standard RS232 communications and labeled RS-232 Port. The second port is relay contact closure configured for standard AS 400 ports. This port is labeled Control Port. The pinout for the RS-232 port is depicted per the chart below. Note: when using the SNMP option card, this port will be disconnected.
Unistar Sx Series UPS Form No.
Unistar Sx Series UPS Form No. 003-2077 If your unit should have a problem, please call our Customer Service department to resolve any issues. Please call, 866-261-1191 or 937-253-1191 and ask for Technical Support. When you call with a problem, please be prepared to provide the following information to the technician.
Unistar Sx Series UPS Form No. 003-2077 Diagnostic Error Codes for 2KV A, 3KV A, 5KV A, 7KV A units 2KVA, 3KVA, 5KVA, 7KVA Error E00 E01 E02 E03 E05 E07 E08 E10 E11 E12 E14 E15 E16 E17 E22 E23 E25 E26 E32 E33 E40 E42 E53 E54 E60 E63 E67 E68 E69 E78 E80 E81 E82 E83 E84 Description System ROM check sum error. System RAM data read/write error. System EEPROM data read/write error. Communication fail between CPU & DSP Temperature over 100oC. Battery voltage is over specification (AC mode).
Unistar Sx Series UPS Form No. 003-2077 6 REPLACING THE BA TTER Y BATTER TTERY REPLACING THE BA TTER Y BATTER TTERY (Must be performed by Authorized Service Personnel ONLY) The Tower Series UPS has a replacable battery(s), however the unit must be turned off, disconnected from utility and discharged prior to changing the batteries. The Rack Mount Series UPS has a hot swappable battery kit. Please read the following warning statements before attempting to service the battery(s).
Unistar Sx Series UPS Form No. 003-2077 CAUTION: System voltages range from 24 VDC to 288 VDC. A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries: 1. 2. 3. 4. 5. 6. Remove watches, rings, or other metal objects. Use hand tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or other metal parts on top of batteries.
Unistar Sx Series UPS Form No. 003-2077 Battery Replacement Procedure for T ower Model Tower (Must be performed by Authorized Service Personnel ONLY) PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES These units are not hot-swappable. Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. 1. Turn off the equipment that is plugged into the output receptacles of the UPS. 2. Turn off the UPS using the primary power switch on the front. 3.
Unistar Sx Series UPS Form No. 003-2077 Battery Replacement Procedure for Rack Mount Models (Must be performed by Authorized Service Personnel ONLY) PLEASE READ THE CAUTIONS BEFORE ATTEMPTING T O REPLACE THE BA TTERIES TO BATTERIES These units are hot-swappable. Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. 1.
Unistar Sx Series UPS Form No. 003-2077 7 OBT AINING SER VICE OBTAINING SERVICE IF THE UPS REQUIRES SERVICE 1. Use the TROUBLESHOOTING section to eliminate obvious causes. 2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax Customer Service at the following numbers; Voice phone 937-253-1191 ext. 141, FAX line 937-253-1723.
Unistar Sx Series UPS Form No.
Unistar Sx Series UPS Form No.
Unistar Sx Series UPS Form No. 003-2077 Customized Output Receptacle Panels The Unistart Sx series UPS has a replacable receptacle panel. The receptacle panel can be configured with multiple choices of receptacles. This will allow the user to customize the output receptacles for their specific applications. Staco Energy Products Co. will only use UL or CE approved receptacles.
Unistar Sx Series UPS Form No. 003-2077 10 LIMITED PRODUCT W ARRANTY WARRANTY STACO ENERGY PRODUCTS CO. (STACO), Dayton, Ohio, warrants this equipment, when properly applied and operated within specified conditions, to be free from defects in material and workmanship for a period of one year from the date of shipment from a STACO ENERGY PRODUCTS CO. warehouse on repair.