Spec Sheet
Minuteman® Encompass On-line UPS Specification
www.minutemanups.com | www.sizemyups.com
© Copyright 2018, Para Systems, Inc. Product specications are subject to change without notice. Minuteman and 
Minuteman Platinum Protection Plan and Encompass are registered trademarks and SentryHD is a trademarks of 
Para Systems, Inc. 
PN-34000528- 12-2018
RoHS
2
COMPLIANT
UPS Model 
EC1000RT2U 
EC1000LCD 
EC1500RT2U 
EC1500LCD 
EC2000RT2U 
EC2000LCD 
EC3000RT2U 
EC3000LCD 
General 
Topology 
Double-conversion, On-line, True Sine Wave Output 
VA Rating 
1,000VA 
1,500VA 
2,000VA 
3,000VA 
Load Capacity 
900 Watts 
1,350 Watts 
1,800 Watts 
2,700 Watts 
Power Factor 
0.9 
Input 
5-15P 
5-20P 
L5-30P 
Power Cord Length  
10-ft. Power Cord  
6-ft. Power Cord 
10-ft. Power Cord  
6-ft. Power Cord 
10-ft. Power Cord  
6-ft. Power Cord 
Receptacles 
(6) 5-15R 
(6) 5-15/20R 
(8) 5-15/20R 
(6) 5-15/20R / (1) L5-30R 
(8) 5-15/20R / (1) L5-30R 
Installation Type 
Rack/Tower 
Tower or Floor 
Input 
Nominal Voltage 
120VAC 
Acceptable Input Voltage 
0 – 160VAC 
Frequency Range 
50/60Hz, ±6Hz, Auto-sensing 
Power Factor Correction 
≥99% at full load 
Efficiency 
>89% Full Load, On-line Mode (AC – AC) 
>96% Full Load, Economy Mode 
Output (Non-battery Operation) 
Voltage Default 
120VAC (110/127VAC adjustable) 
Voltage Regulation 
±2% of nominal voltage 
Frequency Range 
50/60Hz, ±6Hz 
Efficiency (Line Mode) 
>89% (Full Load) 
Output (Battery Operation) 
Nominal Voltage 
120VAC (110/127VAC adjustable) 
Voltage Regulation 
Nominal ±2% (until Low Battery Warning) 
Frequency 
50/60Hz, ±0.2Hz (unless synchronized to utility) 
Voltage T.H.D. 
≤3% (Full Linear Load) 
Batteries 
Battery Type 
Sealed, non-spillable, maintenance-free, valve-regulated lead acid 
Replacement Module 
BM0069 
BM0076 
BM0070 
BM0077 
BM0071 
BM0078 
Runtime (Half Load) 
10 minutes 
15 minutes 
10 minutes 
10 minutes 
Runtime (Full Load) 
2 minutes 
5 minutes 
3 minutes 
3 minutes 
Environmental 
Operating Temp. (Max) 
0° to 40°C (+32° to +104°F) 
Operating Humidity 
10% to 90% Non-condensing 
Operating Elevation 
0 to 3,000m (0 to +10,000 ft.) 
Regulatory Compliance 
Safety and Approvals 
cULus (UL1778 5
th
 Edition & CSA 22.2 no. 107.3-14 /R: 2014) 
FCC Class A, CE certified, RoHS2 (EU Directive 2015/863/EU) 
Rack/Tower Model 
EC1000RT2U 
EC1500RT2U 
EC2000RT2U 
EC3000RT2U 
Physical 
Unit Size (L x W x H) 
(with rack ears installed) 
16” x 18.9” x 3.5” 
407 x 479 x 88mm 
19.2” x 18.9” x 3.5” 
487 x 479 x 88mm 
23.7” x 18.9” x 3.5” 
602 x 479 x 88mm 
Unit Weight 
24.3 lbs. / 11 Kgs. 
44.1 lbs. / 20 Kgs. 
59.5 lbs. / 27.0 Kgs. 
Tower Model 
EC1000LCD 
EC1500LCD 
EC2000LCD 
EC3000LCD 
Physical 
Unit Size (L x W x H) 
15.9” x 6.1” x 10.2” 
403 x 154 x 258mm 
17.4” x 6.8” x 11.4” 
440 x 171 x 288mm 
22.4” x 7.6” x 12.6” 
567 x 192 x 320mm 
Unit Weight 
28.2 lbs. / 12.8 Kgs. 
48.1 lbs. / 21.8 Kgs. 
73.0 lbs. / 33.1 Kgs. 
Extended Battery Packs (For LCD models only) 
BP Part Number 
BP24XL 
BP48XL 
BP72XL 
These products can expose you to chemicals, including lead and lead compounds, which is known to the State of California to cause 
cancer and birth defects or other reproductive harm. For more information, go to www.P65warnings.ca.gov/product