1.2 PRODUCT SPECIFICATION
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Input OutputPower Rating Model
No.
Frequency
(HZ)
Voltage Current Voltage Current
CP500 60 120VAC 6.0A 120VAC 4.2ACP500
Series
500VA/350W
CP500/2 50 220VAC 3.1A 220VAC 2.3A
CP1K 60 120VAC 11A 120VAC 8.3ACP1K
Series
100VA/700W
CP1K/2 50 220VAC 6.2A 220VAC 4.5A
CP2K/2
200VA/1400W
CP2K/2 50 220VAC 8.3A 220VAC 9.1A
CP3K/2
3000VA/2100W
CP3K/2 50 220VAC 12.0A 220VAC 13.6A
NOTE: The power factor of CP2K/2 and CP3K/2 is 0.97.
INPUT
Input Frequency Range: ± 5%
Input Voltage Range: + 10%, - 15%
OUTPUT
Output Frequency Regulation: Phase lock to input under normal condition
± 0.5% at free running.
Output Voltage Regulation: ± 2%
Distortion: Less than 3% under linear load.
BYPASS TRANSFER TIME
UPS Failure: 2.5 ms typical, 4 ms max. (from inverter to bypass and vice
versa).