User`s manual

SNMP-NET
6
Configuring the SNMP-NET by EzSetting
1. Prepare a workstation (Microsoft Windows 9x, Me, NT4.0, 2000, 2003, XP or later).
2. Make sure both the DIP-switches of SNMP-NET are set to OFF position (default: normal
mode) to enable network transmission.
3. Make sure the workstation and SNMP-NET device are in the same LAN.
4. Put the CD (provided) in the CD-ROM drive and find the SNMP-NET EzSetting program then
launch it.
5. Press the Discover button to search for all of the UPS’ in the LAN. All of the UPS SNMP
DEVICE will be listed in the Device List. (See 2-1)
Figure 2-1 EzSetting screen.
6. If the SNMP-NET device cannot be found, check the networking port UDP 3456 in the OS.
Open it if it is blocked.
7. Select the device in the device list to configure the network parameters then press the Modify
button to provide your account and password. The default account and password are
admin and password. (See 2-2)
Figure 2-2
Provide the account and password.