10. Cascading SRPS units
You can cascade up to 16 SRPS units (1 Manager + 15 Slaves). Each SRPS must
have its own unique ID number and the ID numbers must also be in a logical
sequence. The default ID number of the Manager SRPS is 1. The default ID
number of all Slave SRPS units is 16. So to be in a logical sequence where there is
1 Slave, change the Slave ID number to 2. For each additional Slave give it the
next number - ID no 3, then 4 etc.
Changing 1 Slaves ID number
1. Power off the SRPS Manager and Slave unit.
2. Connect the SRPS Manager to a computer using the Serial cable.
3. Plug a Terminator into one of the SRPS Managers iLINK ports and one into
one of the Slaves iLINK ports. See Figure 12.
RING ON
& RESET
iLINK
i i i
i
i i
I
0
A B
C
D E F
H
9
1
10
99
1112
95
1314
67
1516
8
G
ii
RING ON
& RESET
iLINK
i i i
i
i i
L
N
K
P
W
R
RS232
I
0
A B
C
D E F
H
9
1
10
99
1112
95
1314
67
1516
8
G
ii
RS232 Console Command
Terminators
Figure 12 Connecting the iLink cable
4. Connect the iLink cable to the iLINK ports of the SRPS Manager and Slave
unit. See Figure 12.
5. Power on the SRPS Manager and the Slave.
6. Type the instructions as set out below using a Terminal or terminal emulation
software. See page 7 Operating the system to set up a HyperTerminal. Confirm
the current ID nos. by pasting ^isP003EAD . HyperTerminal responds with
^iSWITCH01, ^iSWITCH16.