Installation Manual Ilumen PIDbox Mini v1.5
2.2 QUALIFICATIONS OF SKILLED PERSONS
The work described in this document must be performed by skilled personnel only. Skilled
personnel must have the following qualifications:
Knowledge of how an inverter works and how it is operated
Training in how to deal with the dangers and risks involved in installing and operating
electrical devices and plants
Training in the installation and commissioning of electrical devices and plants
Knowledge of all applicable standards and directives
Knowledge and observance of this document and all safety precautions
2.3 SAFETY PRECAUTIONS
2.3.1 ELECTRIC SHOCK
When the Ilumen PIDbox mini is in operation, voltage will be present. Prior to
maintenance work on the PV plant switch off the Ilumen PIDbox mini.
When you want to change the arrangement of the Ilumen PIDbox mini you must switch
off the Ilumen PIDbox mini 20 minutes prior to making any changes.
2.3.2 ELECTROSTATIC DISCHARGE
Never operate the Ilumen PIDbox mini when not properly installed or when the
components are not closed properly. Always make sure the grounding of the Ilumen
PIDbox mini is done correctly.
3 SCOPE OF DELIVERY
1. 1 x Ilumen PIDbox mini
2. 1 x DC power supply
3. 1 x Power cord (AC plug)
4. 4 x Rubber feet
5. 2 x Mounting bracket
6. 1 x Installation manual
4 PRODUCT DESCRIPTION
The Ilumen PIDbox mini is placed between the inverter and the solar array strings. The power of
the strings goes through the PIDbox, entering on one side “PV in” and leaving on the other “Inv.
out”. This means the Ilumen PIDbox mini is placed in series between the PV panels and the
inverter. You can use one Ilumen PIDbox mini per 2 MPP trackers.