Specifications Instruction Manual

EMCP 3.2
GENERATOR SET CONTROLLER
LEHE4942-02 2
Set points & software are stored in nonvolatile
memory, preventing loss during a power outage.
Compatibility with both mechanical and
electronic engines makes it versatile.
True RMS sensing ensures AC metering accuracy
to within ± 1% of rated AC voltage (L-L and L-N)
and current.
kW and kVA metering to within ± 5% of rating.
Three levels of security allow for configurable
operator privileges.
Single, standard 70-pin connector
COMMUNICATION
J1939 (Primary Data Link)
J1939 #2 (Accessory Data Link)
MODBUS RTU (1/2 duplex); RS-485
(Customer Communication)
ENVIRONMENTAL SPECIFICATIONS
Environmentally sealed front face rated for
IP56. Resistant to chemical splash, including:
diesel fuel, engine oil and machine oil.
Protection level IP22 for rear of controller
Resistant to salt spray
Vibration: withstands 4.3G @ 24-1000 Hz
Shock: withstands 15G
Monitoring Functionality & Controls
Operational from –40° C to 70° C
(40°Fto158°F)
Display Operational from –20° C to 70° C
(–4° F to 158° F)
Storable from –40° C to 85° C (–40° F to 185° F)
0 to 95% Humidity, non-condensing from 30° C
to 60° C (86° F to 140° F)
STANDARDS
UL Recognized
CSA C22.2 No.100,14, 94
Complies with all necessary standards for
CE Certification
98/37/EC Machinery Directive
– BS EN 60204-1 Safety of Machinery
89/336/EEC EMC Directive
– BS EN 50081-1 Emissions Standard
– BS EN 50082-2 Immunity Standard
73/23/EEC Low Voltage Directive
– EN 50178 LVD Standard
ISO3046, ISO8528
IEC529, IEC60034-5, IEC61131-3
MIL STND 461
CONTROLS
Auto/Start/Stop
Engine Cool-Down timer
Emergency Stop
Engine Cycle Cranking
Lamp Test
Generator Voltage
Engine Speed/Generator Frequency
DIGITAL (LCD) INDICATION
Generator AC Voltage – 3 phase (L-L & L-N)
Generator AC Current (per phase & average)
Generator Power kW (total & per phase)
Generator kVAR (total & per phase)
Generator kVAR-hr (total)
Generator % of rated power (total)
(kW, kVA, kVAR)
Generator kVA (total & per phase)
Generator kW-hr (total)
Generator Power Factor (PF)
(average & per phase)
Generator Frequency
Engine RPM
Battery Voltage
Engine Hours
Engine Successful Start Counter
Engine Oil Pressure
Engine Coolant Temperature
Engine Crank Attempt Counter
Service Maintenance Interval
(Engine Operating Hours or Calendar Days)
Real Time Clock
Twenty (20) Event Fault Log
Notes:
1. Temperature indications are viewable in either
°C or °F (operator selectable)
2. Pressure indications are viewable in psi, kPa,
or bar
3. Fuel Consumption viewable in US/Imperial
gal/hr or Liters/hr
FEATURES/BENEFITS (CONT’D) STANDARD FEATURES