Selected Model
Engine: 3516 Generator Frame: 826 Genset Rating (kW): 2000.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 2628110 Genset Rating (kVA): 2500.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 3007.0
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 38699 /38433 /38580 /3636
Generator Output Characteristic Curves
Zero Power Factor Curve
Field
Current
Line -
Line Volt
49.1
0
61.2 240
63.5
288
66.6
336
71.5 384
80.5
432
99.2
480
139.6 528
229.7
576
432.9
624
Air Gap Curve
Field
Current
Line -
Line Volt
0.0 0
9.6
288
11.2
336
12.9 384
14.5
432
16.1
480
17.7 528
19.3
576
20.9 624
22.5
672