User guide
Selected Model
Engine: 3516 Generator Frame: 826 Genset Rating (kW): 2000.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 2628110 Genset Rating (kVA): 2500.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 3007.0
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 38699 /38433 /38580 /3636
Generator Output Characteristic Curves
Open Circuit Curve
Field
Current
Line -
Line Volt
0.0
0
9.8 288
11.6
336
13.6
384
16.1 432
19.8
480
26.3
528
38.8 576
65.4
624
124.0
672
Short Circuit Curve
Field
Current
Armature
Current
0.0 0
29.5
1,804
34.4
2,105
39.3 2,406
44.2
2,706
49.1
3,007
54.0 3,308
58.9
3,608
63.8 3,909
68.7
4,210
Page
5
of
10
Caterpillar Generator Data
05/09/2006