User guide
Selected Model
Engine: 3516 Generator Frame: 826 Genset Rating (kW): 2000.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 2628110 Genset Rating (kVA): 2500.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 3007.0
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 38699 /38433 /38580 /3636
Starting Capability & Current Decrement
Motor Starting Capability (0.4 pf)
SKVA
Percent
Volt Dip
299
2.5
614
5.0
946 7.5
1,296
10.0
1,666
12.5
2,059 15.0
2,474
17.5
2,916
20.0
3,387 22.5
3,888
25.0
4,425
27.5
4,999 30.0
5,617
32.5
6,281
35.0
6,999 37.5
7,777
40.0
Current Decrement Data
E Time
Cycle
AMP
0.0
21,487
1.0 13,737
2.0
12,705
3.0
12,262
4.0 11,879
5.0
11,513
7.5
10,651
10.0 9,861
12.5
9,136
15.0
8,471
20.0 7,301
25.0
6,316
30.0
5,614
35.0 5,973
40.0
6,497
45.0
7,012
Instantaneous 3 Phase Fault Current: 21487 Amps Instantaneous Line - Line Fault Current: 18949 Amps
Instantaneous Line - Neutral Fault Current: 29765 Amps
Page
4
of
10
Caterpillar Generator Data
05/09/2006
http://tmiweb.cat.com/tmi/servlet/cat.edis.tmiweb.gui.TMIDirector?Action=buildtab&tab
...