User guide
Selected Model
Engine: 3516 Generator Frame: 826 Genset Rating (kW): 2000.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 2628110 Genset Rating (kVA): 2500.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 3007.0
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 38699 /38433 /38580 /3636
Generator Cooling Requirements -
Temperature - Insulation Data
Cooling Requirements: Temperature Data: (Ambient 40
0
C)
Heat Dissipated:
64.0 kW Stator Rise:
105.0
0
C
Air Flow: 0.0 m
3
/min Rotor Rise: 105.0
0
C
Insulation Class: H
Insulation Reg. as shipped: 100.0 MO minimum at 40
0
C
Thermal Limits of Generator
Frequency: 60 Hz
Line to Line Voltage: 480 Volts
B BR 80/40 2127.0 kVA
F BR -105/40 2563.0 kVA
H BR - 125/40 2813.0 kVA
F PR - 130/40 2813.0 kVA
Page
3
of
10
Caterpillar Generator Data
05/09/2006
http://tmiweb.cat.com/tmi/servlet/cat.edis.tmiweb.gui.TMIDirector?Action=buildtab&tab
...