Specifications

II.
Power Required
Transducer
Range
output
Set Points
Set Point Hysterisis
Response Time
Time Delay
Repeatability
Temperature Effects
Temperature Range
Separation
SPECIFICATIONS
115 VAC + 10% 40 Hz at 6VA
-
Barium Titanate element C.P.V.C.
outer housing and polyurethane
radiating face.
Optional face materials are
available.
Transducer rated for Class I,
Groups A, B, C, D, &'Class II
Groups F & G.
1.5 to 10.0 feet
0.45 to 3.1 meters
Two (2) Form C,
S.P.D.T. contacts
rated 10A 115VAC non-inductive
Two (2) independently adjustable
throughout the range
0.5 inch per ft.
of range when in
alarm mode
0.5 sec.
without time delay
Selectable 3 or 10 seconds
Better than 0.1% (l/16"' on 5' range
or l/8" on 10' range)
Setpoint varies -0.17% of range/°C
deviation from calibration temperature
Electronics -2OO°C to +60°C
o'+140°F)
Transducer
'-5 t
-40°C to +93°C
(-40 to +200°F)
Maximum distance from transducer to
electronics is 183M (600 ft.) using
RG-62U co-axil cable
2-l