Specifications
IV.
INSTALLATION
1.
Electronic Package
The electronic circuits of the Level Genie Ultrasonic
Level Switch are contained on a single printed circuit
motherboard.
A Nema 12 enclosure is supplied.
Refer to Fig. 1
for outline and mounting dimensions.
Separate 1/2"
conduits should be installed for the power
wiring and the transducer cable.
The transducer cable must not
be installed in a conduit with other wiring.
Fig.
3 indicates
proper terminal connections for the electronics.
Note, that
the power input must include a good electrical ground.
Since the Level Genie is designed for continuous operation,
a power switch has not been provided.
If one is desired it may
be included in the external power circuit.
2. Pre Start-Up Checks
(A) Unit Synchronization
To avoid cross talk between multiple units located in the
same panel or with common transducer runs, the units must be
synchronized.
(They must transmit simultaneously).
To synchronize any number of units, series connect terminal
10,marked "SYNC", with jumpers from unit to unit.
(B) Program Module
Be sure the program module is installed in the correct
orientation.
(With the rounded corner toward the top of the
circuit board).
(C) Switch SW1
The "RUN -
CAL" toggle should be in the "CAL" position to
4-1