Totalization, P619 - P648
The following parameters are specific to the use to the BW100 totalizers.
Refer also to Operation\Totalization.
If the resolution (P631 - P639) selected would cause the
totalizer to lag behind the count rate, a message E2
is displayed after making the entry.
Select a greater resolution value.
e.g. given: P005 = 1 (t/h)
P631 = 5
then: totalizer count increments by 10 for each 10 metric
tonne registered
P619 totalizer drop out
This parameter sets the limit, in percent of design rate, below which
material rates are not totalized.
The value of ’0’ is reserved to allow both negative and positive totalization.
enter drop out value in % of design rate
P631 totalizer 1 resolution, internal
This parameter sets the resolution of internal totalizer 1.
entry: 1 = 0.001 (one thousandth)
2 = 0.01 (one hundredth)
3 = 0.1 (one tenth)
4 = 1 (unit)
5 = 10 (x ten)
6 = 100 (x hundred)
7 = 1000 (x thousand)
PARAMETER DESC.