TOTALIZATION
The totalization function is based on the internal rate (mass per unit time) signal
proportional to belt speed and load on the associated belt scale. It is not affected
by the damping function (P080). The rate signal is sampled several times a second
to accurately count the mass of material conveyed. The count is held in the master
totalizer used to increment the internal totalizers and to produce a pulse signal for
the remote totalizers.
The BW100 provides four separate totalizer functions: internal totalizer 1, internal
totalizer 2, remote totalizer 1 and remote totalizer 2.
To avoid totalizing material at low flow rates, the totalizer drop out limit (P619) is set to
a percentage of the design rate. Below this limit, totalization stops. When material flow
returns to a rate above the drop out limit, totalization resumes.
Totalizer resolution or count value is set by the respective control parameters, P631 -
P639. If the resolution selected causes the totalizer to lag behind the count rate, an
E2 error is displayed after making the parameter entry. The error is rectified by
selecting a greater resolution value.
e.g.:
internal totalizer
1
given: P005 = 1 (t/h)
P631 = 5
then: totalizer count increments by 10 for each 10 metric tonnes registered
external totalizer
1
given: P005 = 1 (t/h)
P638 = 5
then: contact closure occurs once for every 10 metric tonnes registered
For remote totalization, the contact closure duration is set by the respective control
parameters, P643 and P644. The value is automatically calculated upon entry of the
design rate (P011) and remote totalizer parameters (P638 and P639), so that the
duration of contact closure allows the relay response to track the total up to the design
rate. The value can be changed to suit specific contact closure requirements, such as
in the case of programmable logic controllers. If an E2 error is displayed, P638 or
P639 has to be increased.
The totalizers are reset through the master reset (P999), the totalizer reset (P648) or
through the keypad.
» master reset: the reset of all totalizer functions is included in the master reset.
» totalizer reset: totalizer reset can be used to resets internal totalizers
1 and 2, or totalizer 2 independently.
» keypad: pressing simultaneously while in the run mode
resets internal totalizer 1, as well as the internal counts
for both remote totalizers.
Placing the internal totalizers on to the display scroll of the run mode is controlled by
the totalizer display parameter (P647); displaying either one or both totalizers.