WIRING FORMATS (cont’d)
MillBus / Multiple BIC-II Interconnection
1. One 100 Ω MillBus loop termination resistor is supplied with each BIC-II. For single BIC-II operation,
the resistor is connected to TB2 - 4/5. For multiple BIC-II operation, connect the 100 Ω resistors to
the unused MillBus connections, TB2 - 1/2 of BIC-II #1 and TB2 - 4/5 of the last BIC-II.
2. The maximum number of BIC-II’s per Millbus is 31.
3. The MillBus circuitry utilizes an isolated power supply. Shield connection TB2 - 3 is either isolated
from chassis ground when J1 - 2/3 is jumpered or tied to chassis ground when J1 - 1/2 is jumpered.