Instruction manual
Port Initialization
A Port Initialization prepares the BIC-II to communicate with a Milltronics product. Write a Port Initialization
message for each BIC-II product port used, before attempting to Read/Write product data.
The product port will remain initialized indefinitely, however it is recommended, the Port Initialization registers
be read and verified following: power up, power resumption, or erroneous data.
If the product (or product baud rate) is changed, write a new Port Initialization. If a product is disconnected,
write a Port Initialization using Product code 00, to disable the Port.
BIC-II Port 1 is default initialized for AiRanger XPL communications.
Port Initialization register (47001 to 47006) bit map, (last register digit = product port number):
bits 15 to 8 contain the Product code: 00 = none (off)
03 = AiRanger IV (AIR4)
04 = AiRanger DPL (DPL)
05 = LiquidRanger (LIQUID)
06 = AiRanger XPL (XPL)
08 = CompuScale or CompuFlo series integrator (COMPUX)
09 = AiRanger XPL Plus
0A = Airanger DPL PLus
bits 7 to 4 contain the TX code: 1 to F (number of transmits per message)
bits 3 to 0 contain the Baud code: 4 = 300
6 = 1200
7 = 2400
A = 4800 Refer to the product instruction
C = 9600 manual for applicable value(s)
E =19200
example: Write a message with Address Field 01 and Data Field 0327 to register 47002
(Port 2 initialization).
Address = 01 (BIC-II I.D. # 1)
Register = 47002 (Port 2)
Product = 03 (AIR4)
TX = 2 (Transmit all sends to AIR4/LIQUID twice)
Baud = 7 (2400)
recommended action:Read BIC-II # 1 register 47002 to verify the Port Initialization.
96/01/09
PL-371 9 – 3