Owner`s manual
OM-2226 Page 24
Y Disconnect and lockout/tag-
out input power before con-
necting input conductors
from unit.
Y Have only qualified persons
make this installation.
Check input voltage available at
site.
1 Line Disconnect Device
2 Input And Grounding
Conductors
See Section 3-13.
For three-phase opera-
tion:
Y Always connect green or
green/yellow wire to supply
grounding terminal, never to
a line terminal.
Connect black, white, and red wires
(L1, L2, L3) to line terminals.
For single-phase opera-
tion:
Y Always connect green or
green/yellow wire to supply
grounding terminal, never to
a line terminal.
3 Black And White Input
Conductor
4 Red Input Conductor
5 Insulation Sleeving
6 Electrical Tape
Insulate and isolate red conductor
as shown.
Note: This unit is equipped with
Auto-Linet. The Auto-Line circuit-
ry automatically connects to
120–460 VAC, single- or three-
phase power without removing the
cover to relink the power source.
L1
1
1
2
2
3
2
6
5
4
L2
L3
L1
L2
Y Always connect grounding
conductor first
1
3
= GND/PE
Green Or
Green/Yellow
Green Or
Green or
Green/Yellow
input_2 3/96 - ST-802 454
3-14. Connecting Input Power
Green/Yellow
Install conductors into a deen-
ergized line disconnect device.