User Manual
Table Of Contents
- RK-5409-5 Reference Kit for 916 MHz MeshScape™ Systems
- Contents
- About This Guide
- 1: Introduction
- 2: Installing the MeshScape System
- 3: Running MeshScape Network Monitor
- MeshScape Network Monitor Overview
- Configuring a Node’s Operation
- Configuring Sample Interval of Single Node
- Configuring Sample Interval of all Network Nodes
- Configuring Digital I/O Operation
- Configuring UART Operation
- Configuring AD (analog-to-digital) Converter Operation
- Configuring RS-232 Operation (MN-5409 only)
- Configuring RS-485 Operation (MN-5409 only)
- Using Watch Function to Display Configuration Information
- Labeling an End Node or Mesh Node
- Configuring Persistence Attributes
- Selecting a Com Port on the Host PC
- Configuring Serial and ADC Data Formats
- Turning Event Tracking On/Off
- Broadcasting Data to All Nodes.
- Creating an Event Log File
- Viewing the Contents of an Event Log File
- Viewing MeshScape Statistics
- 4: Using the MeshScape API
- A: Sample Application
- B: Performing Firmware Upgrades and Configuring Device IDs
- Glossary
- Index
RK-5409-5 Reference Kit User’s Guide B-11
Performing End Node Configurator Operations
The default end node sample interval setting is 60 seconds.
6. Enter the rate at which the end node sends statistics in the Statistics Reporting Rate
field.
The Statistics Reporting Rate is the number of normal packets transmitted before
performance statistics are added to a packet.
A Statistics Reporting Rate of 0 means every packet has performance statistics added
to it. A Statistics Reporting Rate of 1 means 1 normal packet is transmitted then
performance statistics are added to a packet. A Statistics Reporting Rate of 2 would
mean 2 normal packets are transmitted and the next packet has performance
statistics added to it.
The maximum Statistics Reporting Rate is 254.
The default setting is 0—every packet has performance statistics added to it.
7. Click Program to program the end node with the entered settings.