13. Cycle end conditions
Nr
Cycle end conditions (cell Setup 45)
SF45=0
Timeout (time elapsed)
SF45=1
Cycle ends when temperature setpoint is exceeded in channel 1 (boiler)
SF45=2
Cycle ends when temperature setpoint is exceeded in channel 2 (bar)
SF45=3
Cycle ends when temperature setpoint is exceeded in channel 3 (shell)
SF45=4
Cycle ends after the preset time is elapsed or temperature setpoint is exceeded (boiler)
SF45=5
Cycle ends after the preset time is elapsed or temperature setpoint is exceeded (bar)
SF45=6
Cycle ends after the preset time is elapsed or temperature setpoint is exceeded (shell)
SF45=7
Cycle ends after the preset time is elapsed and temperature setpoint is exceeded (boiler)
SF45=8
Cycle ends after the preset time is elapsed and temperature setpoint is exceeded (bar)
SF45=9
Cycle ends after the preset time is elapsed and temperature setpoint is exceeded (shell)
SF45=10
Cycle ends when the boiler temperature drops below the setpoint
SF45=11
Cycle ends when the bar temperature drops below the setpoint
SF45=12
Cycle ends when the shell temperature drops below the setpoint
SF45=13
Cycle ends after the preset time is elapsed or the boiler temperature drops below the setpoint
SF45=14
Cycle ends after the preset time is elapsed or the bar temperature drops below the setpoint
SF45=15
Cycle ends after the preset time is elapsed or the shell temperature drops below the setpoint
SF45=16
Cycle ends after the preset time is elapsed and the boiler temperature drops below the setpoint
SF45=17
Cycle ends after the preset time is elapsed and the bar temperature drops below the setpoint
SF45=18
Cycle ends after the preset time is elapsed and the shell temperature drops below the setpoint
SF45=19
End of a cycle, when the pasterisation number is reached.
SF45=20
End of a cycle, when either the pasterisation number or the set time is reached.
SF45=21
End of cycle when, after reaching the bar temperature, the set time is counted down.