User Manual

Controller user's manual INDU-50 v1.95(86)EN
www.mikster.eu
| 17
SF80
0
0..5
Selection of sterilisation coefficients table for:
0 coefficient z=4,8 K
1 coefficient z=7,78 K
2 coefficient z=10 K
3 coefficient z=15 K
4 coefficient z=25 K
5 coefficient z=33,34 K
SF81
52°C
0..100°C
Temperature, from which the governor starts counting the
pasterisation number
SF82
SF83
SF84
0
1
2
0..2
0 ..2
0..2
Number of the measuring channel versus which the regulation is
carried on governor 1
Number of the measuring channel versus which the regulation is
carried on governor 2
Number of the measuring channel versus which the regulation is
carried on governor 3
0 measuring channel 1
1 measuring channel 2
2 measuring channel 3
SF85
SF86
SF87
0
0
0
-50..100°C
-50..100°C
-50..100°C
Shifting of the set temperature for governor 1
Shifting of the set temperature for governor 2
Shifting of the set temperature for governor 3
SF88
0
0..4
Process triggering method
0 START key
1 Input 1
2 Input 2
3 Input 1 or 2
4 Input 1 or 2
SF89
0
0..1
Measurement recording frequency unit (applies to SF49):
0 min
1 sec
SF90
0
0..1
Time display method
0 countdown
1 forward countdown
SF91
SF92
SF93
10 s
10 s
10 s
10..1000 s
10..1000 s
10..1000 s
Cycle time of digital output - Governor PID1
Cycle time of digital output Governor PID2
Cycle time of digital output Governor PID3
SF94
SF95
SF96
0 s
0 s
0 s
0..120 s
0..120 s
0..120 s
Minimum heating time Governor PID1
Minimum heating time - Governor PID2
Minimum heating time - Governor PID3
SF97
SF98
SF99
0 s
0 s
0 s
0..120 s
0..120 s
0..120 s
Minimum period interval time Governor PID1
Minimum period interval time Governor PID2
Minimum period interval time Governor PID3
SF100
SF101
SF102
0 s
0 s
0 s
0..120 s
0..120 s
0..120 s
Purge time Governor PID1
Purge time Governor PID2
Purge time Governor PID3
SF103
5,2
0..99,9
Relative governor gain
SF104
30 s
0..120 s
Minimum burner start-up time for the relative governor
SF105
30 s
0..120 s
Minimum burner switch-off time for the relative governor