SF63
Off
On / Off
Maximum temperature exceeded alarm activation for channel 1
SF64
Off
On / Off
Maximum temperature exceeded alarm activation for channel 2
SF65
Off
On / Off
Maximum temperature exceeded alarm activation for channel 3
SF66
Off
On / Off
Maximum allowable (alarm) temperature for channel 1
SF67
Off
On / Off
Maximum allowable (alarm) temperature for channel 2
SF68
Off
On / Off
Maximum allowable (alarm) temperature for channel 3
SF69
0
0..4
Alarm activation on control input 1
0 – alarm disabled
1 – alarm when inputs 6-8 are close
2 – alarm when inputs 6-8 are open
3 – keyboard blocking when inputs 6-8 shorted
4 - keyboard blocking when inputs 6-8 not shorted
SF70
0
0..4
Alarm activation on control input 2
0 – alarm disabled
1 – alarm when inputs 7-8 are close
2 – alarm when inputs 7-8 are open
3 – keyboard blocking when inputs 7-8 shorted
4 – keyboard blocking when inputs 7-8 not shorted
SF71
60
0..999 sek
Sensor fault alarm indication delay
SF72
60
0..999 sek
Temperature exceeded alarm indication delay.
SF73
60
0..999 sek
Control input alarm indication delay
SF74
0
0..999
SETUP access code change
Value 0 - code check OFF
SF75
0
0..1
Time base for START mode
0 – hour:min
1 – min:sec
SF76
66,4
0,1..999,
1 min
Set pasterisation number
SF77
72°C
0..100°C
Pasterisation temperature (Process temperature Tr)
SF78
0
0..2
The channel on which the temperature inside the box is measured.
0 – channel 1
1 – channel 2
2 – channel 3
SF79
15
0..600 sek
Setting the reading rate of the pasterisation number (seconds)