User Manual
Controller user's manual INDU-50 v1.95(86)EN
www.mikster.eu
| 15
No.
Default
value
Range
Description
User
settings
SF39
20°C
0..200°C
Regulator activation temperature (Tza) for channel 1
For “setpoint ramping” algorithm
SF40
20°C
0..200°C
Regulator activation temperature (Tza) for channel 2
For “setpoint ramping” algorithm
SF41
20°C
0..200°C
Regulator activation temperature (Tza) for channel 3
For “setpoint ramping” algorithm
SF42
1
0..100 sek
Regulator activation delay [seconds] for channel 1
SF43
1
0..100 sek
Regulator activation delay [seconds] for channel 2
SF44
1
0..100 sek
Regulator activation delay [seconds] for channel 3
SF45
5
0..21
START mode end conditions see “CYCLE END CONDITIONS”
SF46
1
0..1
Recording
0 – continuous recording
1 – recording in the START mode only
SF47
HMd
HMd/HM
AUTOSTART mode parameter format
HMD – hour, minute and daily delay for START
HM – ours and minutes to START
SF48
5
0..10 godz.
Maximum time period after which the controller returns to the
START mode (after power failure)
SF49
1
1..360 min
Measurement recording frequency (unit defined in SF89: min, sec)
SF50
1
1..360 min
Alarm recording frequency
SF51
C
C / F
Temperatur unit
SF52
1 [min]
0..99 [min]
Audible signal duration
Note! If 0 is selected, then the signal is cancelled with the OK key!
SF53
1
0 .. 1
Alarm output operating mode
0 –interrupted signal
1 –continuous signal
SF54
150°C
-99..999°C
Maximum allowable (alarm) temperature for channel 1
SF55
150°C
-99..999°C
Maximum allowable (alarm) temperature for channel 2
SF56
150°C
-99..999°C
Maximum allowable (alarm) temperature for channel 3
SF57
-99°C
-99..999°C
Minimum allowable (alarm) temperature for channel 1
SF58
-99°C
-99..999°C
Minimum allowable (alarm) temperature for channel 2
SF59
-99°C
-99..999°C
Minimum allowable (alarm) temperature for channel 3
SF60
Off
On / Off
Sensor fault alarm activation for channel 1
SF61
Off
On / Off
Sensor fault alarm activation for channel 2
SF62
Off
On / Off
Sensor fault alarm activation for channel 3